Skip to content

The Edge of the Cyber World See the latest

Cyber Security

All-Line Equipment Company Fuel-Boss

View CSAF

Summary

Successful exploitation of these vulnerabilities could allow attackers to execute arbitrary commands or code remotely on affected systems.

The following versions of All-Line Equipment Company Fuel-Boss are affected:

  • Fuel-Boss V1 Standard >=|<=PHP_7.1.5_7.1.5 (CVE-2018-19518, CVE-2019-11043)
  • Fuel-Boss V1 Portal >=|<=PHP_7.1.5_7.1.5 (CVE-2018-19518, CVE-2019-11043)
  • Fuel-Boss V1 Master/Slave >=|<=PHP_7.1.5_7.1.5 (CVE-2018-19518, CVE-2019-11043)
  • Fuel-Boss V1 Backflush Systems >=|<=PHP_7.1.5_7.1.5 (CVE-2018-19518, CVE-2019-11043)
CVSS Vendor Equipment Vulnerabilities
v3 8.7 All-Line Equipment Company All-Line Equipment Company Fuel-Boss Improper Neutralization of Argument Delimiters in a Command (‘Argument Injection’), Buffer Copy without Checking Size of Input (‘Classic Buffer Overflow’)

Background

  • Critical Infrastructure Sectors: Critical Manufacturing, Defense Industrial Base, Emergency Services, Transportation Systems
  • Countries/Areas Deployed: Worldwide
  • Company Headquarters Location: United States

Vulnerabilities

Expand All +

CVE-2018-19518

Fuel-Boss is vulnerable to the University of Washington IMAP Toolkit 2007f on UNIX, used in imap_open() in PHP and other products, launching an rsh command via the imap_rimap and tcp_aopen functions without preventing argument injection, which can allow remote attackers to execute arbitrary OS commands when an untrusted IMAP server name is supplied and rsh has been replaced by a program with different argument semantics such as ssh. This enables attacks through IMAP server names containing a “-oProxyCommand” argument, as well as a stack-based buffer overflow that may allow an attacker to remotely execute arbitrary code.

View CVE Details


Affected Products

All-Line Equipment Company Fuel-Boss
Vendor:
All-Line Equipment Company
Product Version:
All-Line Equipment Company Fuel-Boss V1 Standard: >=|<=PHP_7.1.5_7.1.5, All-Line Equipment Company Fuel-Boss V1 Portal: >=|<=PHP_7.1.5_7.1.5, All-Line Equipment Company Fuel-Boss V1 Master/Slave: >=|<=PHP_7.1.5_7.1.5, All-Line Equipment Company Fuel-Boss V1 Backflush Systems: >=|<=PHP_7.1.5_7.1.5
Product Status:
known_affected
Remediations

Vendor fix
Fixes are available for the Fuel-Boss V1 Standard and Fuel-Boss V1 Portal. Please contact All-Line Equipment Company (866-356-3336) for instructions on how to receive these fixes.

Vendor fix
Fixes are not yet available for the Fuel-Boss V1 Master/Slave.

Vendor fix
No fix is planned for Fuel-Boss V1 Backflush Systems.

Mitigation
All-Line Equipment Company recommends either taking products that are not fixed off the Internet or restricting the IP addresses that can access them at the router level.

Relevant CWE: CWE-88 Improper Neutralization of Argument Delimiters in a Command (‘Argument Injection’)


Metrics

CVSS Version Base Score Base Severity Vector String
3.1 7.5 HIGH CVSS:3.1/AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H
4.0 7.7 HIGH CVSS:4.0/AV:N/AC:H/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N

CVE-2019-11043

Fuel-Boss running versions up to and including PHP 7.1.5 is vulnerable because certain FPM configurations allow the FPM module to write past allocated buffers into space reserved for FCGI protocol data, thereby creating a possible remote code execution condition.

View CVE Details


Affected Products

All-Line Equipment Company Fuel-Boss
Vendor:
All-Line Equipment Company
Product Version:
All-Line Equipment Company Fuel-Boss V1 Standard: >=|<=PHP_7.1.5_7.1.5, All-Line Equipment Company Fuel-Boss V1 Portal: >=|<=PHP_7.1.5_7.1.5, All-Line Equipment Company Fuel-Boss V1 Master/Slave: >=|<=PHP_7.1.5_7.1.5, All-Line Equipment Company Fuel-Boss V1 Backflush Systems: >=|<=PHP_7.1.5_7.1.5
Product Status:
known_affected
Remediations

Vendor fix
Fixes are available for the Fuel-Boss V1 Standard and Fuel-Boss V1 Portal. Please contact All-Line Equipment Company (866-356-3336) for instructions on how to receive these fixes.

Vendor fix
Fixes are not yet available for the Fuel-Boss V1 Master/Slave.

Vendor fix
No fix is planned for Fuel-Boss V1 Backflush Systems.

Mitigation
All-Line Equipment Company recommends either taking products that are not fixed off the Internet or restricting the IP addresses that can access them at the router level.

Relevant CWE: CWE-120 Buffer Copy without Checking Size of Input (‘Classic Buffer Overflow’)


Metrics

CVSS Version Base Score Base Severity Vector String
3.1 8.7 HIGH CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:N
4.0 9.4 CRITICAL CVSS:4.0/AV:N/AC:H/AT:P/PR:N/UI:N/VC:H/VI:H/VA:N/SC:H/SI:H/SA:N

Acknowledgments

  • These vulnerabilities were anonymously reported to CISA.

Legal Notice and Terms of Use

This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).


Recommended Practices

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities.

Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.

Locate control system networks and remote devices behind firewalls and isolating them from business networks.

When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

These vulnerabilities have a high attack complexity.


Revision History

  • Initial Release Date: 2026-08-27
Date Revision Summary
2026-08-27 1 Initial Publication

Legal Notice and Terms of Use